Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/28/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/12/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE ALL UNUSED GAS LINES 2) INDEX TO DRAWINGS SHOWS C-1 ATTACHED (UNABLE TO LOCATE) 3) EXISTING ELECTRIC STRIP WIRING AT BASE BOARD IS HAZARDOUS 4) PLAN CALLS FOR LOW AND WINDOWS DBL GLAZED 5) PLAN DOES NOT SHOW ELECTRIC RECEPTACLE ADDED IN DINING ROOM, KITCHEN, BEDROOMS ETC... AND BASEMENT 6) NEED TO REMOVE COVER ON NEW J-BOX AND HAVE LADDER TO INSPECT 7) WATER HEATER FLUE PIPE INSTALLATION NOT TO CODE 8) WATER HEATER PRESSURE RELIEF LINE NOT TO CODE 9) WATER HEATER NEEDS APPROVED AGA SHUT OFF VALVE WALLS 10) PLAN DOES NOT SHOW SOME NEW WALLS 11) WILL NEED VERIFICATION OF L-11 LICENSED ELECTRIC CONTRACTOR DOING ALL ELECTRICAL WORK 12) STOPPED INSPECTION 13) INSTALL SMOKE DETECTORS ALL LEGAL BEDROOMS AND HALL 14) PLAN DOES NOT SHOW REMOVAL OF OLD FURNACE 15) WILL NEED HEAT SOURCE ALL HABITABLE ROOMS 16) BASEMENT ROOMS CANNOT BE BEDROOMS-NO APPROVED EGRESS (PLAN SHOWS BEDROOMS) |
|
| 04/11/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED COPY OF APPROVED PLANS 2) NEED COPY OF VIOLATION NOTICE TO DETERMINE WHAT WORK IS BEING DONE OR HAS BEEN DONE 3) NEED SMOKE DETECTORS BEDROOMS & HALLWAYS 4) NEED HEAT SOURCE ALL HABITABLE ROOMS 5) STOPPED INSPECTION |