Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM00843

Parcel: 11016068B


Addresses:

6111 E GRANT RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM00843

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
06/12/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
- CLOSET FLANGES OK
- OVERHEAD PVC OK
- WATER PIPING INSULATED OK
- PROVIDE APPROVAL FROM ARCHITECT FOR WATER PIPING INSTALLED BELOW SLAB.
- PLAN CALLS FOR LAVATORY TO VTR, REVISION NEEDED FOR USE OF AAV
- REPAIR 3" VENT ABOVE ROOF, INSTALL ROOF FLASHINGS, PROTECT EXPOSED PVC FROM UV RAYS.
04/25/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. EAST TOILET ROOM RE-ROUGH OK
OK TO COVER UNDERGROUND ONLY.
2. SUPPORT PVC OVERHEAD.
NEED TO SEE CLOSET FLANGES.
3. YOU HAVE AN ADDRESSING PROBLEM. POSTED ADDRESS IS 6111 E GRANT RD - PERMIT ADDRESS READS 6107 E GRANT RD
PLEASE CORRECT THIS PROBLEM BEFORE THE NEXT INSPECTION.
04/05/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST UNDERGROUND ONLY WASTE & VENT OK
PIPE WRAPS OK
1. NEED TO SEE PERM CAP OF 3" SOIL LINE DEMO AT STOOL IN EAST CORNER.
2. WILL NEED TO SEE NETWORK OF STOOL IN EAST RESTROOM IF REQUIRED PER PLAN.