Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 06/26/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NED AN APPROVED EXTENDER RING 314.20 2) EMERGENCY LIGHTING TO BE CONNECTED TO LIGHTING OF AREA SERVED 700.12 3) FINISH #1 INSPECTION DATED 6/20/06 |
|
| 06/21/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/20/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. AC DISCONNECT NOT TO BE MOUNTED ON ANY ACCESSIBLE PANEL 440.14 2. CONDUCTOR TO BE #1 AS PER PLANS. |
|
| 06/16/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GROUNDING ELECTRODE TAP CONDUCTOR NOT TO BE IN METER SOCKET. 2. USE BONDING JUMPERS ONLY IN METER SOCKET. PAY ATTENTION TO 250.8 & 12 & 66 3. NEED REJECTION PIN. 4. PLEASE HAVE REVISED PLANS ON SITE. |