Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM00843
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/05/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* OK TO TILE |
|
05/30/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. WHEN SUPPORT WIRES ARE USED ATTACH AT BOTH ENDS 300.11 - ALSO INDEPENDENT OF CEILING GRID WIRES. 2. OLD VDV CABLING TO BE AS PER 800.3 & 6, 725.3 & 6 3. BOXES MORE THAN 1/4" FROM SURFACE TO BOX IN TILES TO USE APPROVED EXTENDER RINGS 314.20 4. WE HAVE CONDUCTOR OVERFILL AT BOX. 5. PLEASE VERIFY AUTHORIZATION OF ENT IN CEILING. |
|
05/22/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* LOCKED - NO ACCESS |