Permit: T06CM00836

Parcel: 108203320


Addresses:

4186 N FORTUNE LP

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BEDROOM SMOKE DETECTORS REQUIRE ARC FAULT PROTECTION -- NEC 210.12B
2. SMOKE DETECTOR IN BEDROOOM TO BE 36" MINIMUM FROM VENT -- NFPA 72
3. INSTALL SHOWER TYPE TRIM FOR LIGHT @ SHOWER -
NEC 410.4
4. MAKE SURE ALL 3 - WIRE HOMERUNS HAVE NEUTRALS PIG TAILED - NEC 300.13B
5. KITCHEN COUNTER RECEPTACLE LEFT OF RANGE HAS LOOSE BOX - NEC 406.4
6. KITCHEN COUNTER RECEPTACLE AND DISHWASHER/DISPOSAL NOT TO BE ON SAME CKT -
NEC 210.52 B2, NEC 230
7. FINISH ALARM TRIM