Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BEDROOM SMOKE DETECTORS REQUIRE ARC FAULT PROTECTION -- NEC 210.12B 2. SMOKE DETECTOR IN BEDROOOM TO BE 36" MINIMUM FROM VENT -- NFPA 72 3. INSTALL SHOWER TYPE TRIM FOR LIGHT @ SHOWER - NEC 410.4 4. MAKE SURE ALL 3 - WIRE HOMERUNS HAVE NEUTRALS PIG TAILED - NEC 300.13B 5. KITCHEN COUNTER RECEPTACLE LEFT OF RANGE HAS LOOSE BOX - NEC 406.4 6. KITCHEN COUNTER RECEPTACLE AND DISHWASHER/DISPOSAL NOT TO BE ON SAME CKT - NEC 210.52 B2, NEC 230 7. FINISH ALARM TRIM |