Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/09/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - COMBUSTIBLES NOT ALLOWED IN PLENUMS. - PROVIDE SCREENS IN ROOFTOP VENTS. - PROVIDE PERMANENT ACCESS TO ROOFTOPS WITH WALLS HIGHER THAN 30" AS PER IMC. |