Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 04/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FINISH PREVIOUS ITEMS |
|
| 04/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SWITCHES TO BE GROUNDED ON NEW SWITCHES 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING ON NEW DEVICES. 314.20 3. COUNTER RECEPTACLE NOT WORKING 4. SEPARATE GROUND & NEUTRAL AT RECEPTACLE 5. PROPERLY CONNECT GROUNDING EQUIPMENT CONDUCTOR AT LIGHT FIXTURES. 6. USE APPROVED HARDWARE FOR FIXTURES & DEVICES DRYWALL SCREWS ONLY FOR DRYWALL. 7. WRAP CONDUCTORS UNDER SCREW TERMINALS IN A CLOCKWISE DIRECTION 8. TIGHTEN LOOSE WATER HEATER FITTINGS. |
|
| 04/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |