Permit: T06CM00813

Parcel: 13314460A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
04/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
FINISH PREVIOUS ITEMS
04/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SWITCHES TO BE GROUNDED ON NEW SWITCHES
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING ON NEW DEVICES. 314.20
3. COUNTER RECEPTACLE NOT WORKING
4. SEPARATE GROUND & NEUTRAL AT RECEPTACLE
5. PROPERLY CONNECT GROUNDING EQUIPMENT CONDUCTOR AT LIGHT FIXTURES.
6. USE APPROVED HARDWARE FOR FIXTURES & DEVICES DRYWALL SCREWS ONLY FOR DRYWALL.
7. WRAP CONDUCTORS UNDER SCREW TERMINALS IN A CLOCKWISE DIRECTION
8. TIGHTEN LOOSE WATER HEATER FITTINGS.
04/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*