Permit: T06CM00812

Parcel: 13314460A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/16/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FOUNTAIN
1. JUNCTION BOX AT POLE LIGHT OPEN -- EXPOSED CONDUCTORS & DEVICE.
05/10/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK ALL UNITS
1. FINISH FOUNTAIN ELECTRIC
05/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK SOUTH 1/2 -- 12 UNITS
05/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. USE APPROVED HARDWARE FOR DEVICES -- NOT DRYWALL SCREWS.
2. TIGHTEN LOOSE FITTINGS
3. USE TERMINAL ENDS WITH STRANDED CONDUCTORS UNDER SCREWS
4. BOXES MORE THAN 1/4" FROM SURFACE 314.20
04/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*