Permit: T06CM00812

Parcel: 13314460A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/16/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH ELECTRIC
01/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. DAMAGED A/C SER CABLE UNIT #210
2. CONDUCTOR TO EXTEND 6" OUTSIDE OF BOX - UNIT #210
3. PROTECT CONDUCTOR FROM SCREWS INSIDE
OF BOX - 314.23
4. PROTECT CABLE AT JOIST - #107
5. SPLICE TO BE ACCESSIBLE - #108, 105, 206

OK 106, 109, 110, 208, 209, 205, 207

NOTE: BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20