Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* CHECKED CONDENSATE, PROPER STRAPPING. REMOVE OLD COPPER CONDENSATE FROM SERVE VENT & CAP OFF TEE. OK FOR CEILING TILES RECONNECT SUPPLY DUCT IN RESTROOM WILL CHECK CORRECTIONS ON FINAL. |
|
| 03/28/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* HANGER STRAPS ON FLEX DUCT MUST BE MIN. 1 1/2 WIDE. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. RELOCATE TO AN APPROVED LOCATION. |