Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T06CM00811
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* CHECKED CONDENSATE, PROPER STRAPPING. REMOVE OLD COPPER CONDENSATE FROM SERVE VENT & CAP OFF TEE. OK FOR CEILING TILES RECONNECT SUPPLY DUCT IN RESTROOM WILL CHECK CORRECTIONS ON FINAL. |
|
03/28/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* HANGER STRAPS ON FLEX DUCT MUST BE MIN. 1 1/2 WIDE. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. RELOCATE TO AN APPROVED LOCATION. |