Permit: T06CM00811

Parcel: 13331159W


Addresses:

8822 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T06CM00811

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
CHECKED CONDENSATE, PROPER STRAPPING.
REMOVE OLD COPPER CONDENSATE FROM SERVE VENT & CAP OFF TEE.
OK FOR CEILING TILES
RECONNECT SUPPLY DUCT IN RESTROOM
WILL CHECK CORRECTIONS ON FINAL.
03/28/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
HANGER STRAPS ON FLEX DUCT MUST BE MIN. 1 1/2 WIDE.
CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. RELOCATE TO AN APPROVED LOCATION.