Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM00792
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2006 | FRAMING | Approved | IVRS - Inspection :* | |
06/13/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) FIRE BLOCK TUBS 2) BLOCK REGISTER MASTER BATH 3) ADD FHA STRAP COMPRESSOR LINE KITCHEN 4) NEED MORE SLOPE B-VENT 5) CUT FELT FROM FURNACE B-VENT 6) OK TO INSULATE |
|
06/09/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1. FIREBLOCK TUB 2. INSTALL RED HEADS WHERE MISSING. 3. BLOCK REGISTER MASTER 4. STAPLED #12 WIRE KITCHEN. 5. REATTACH BOX BASE OF STAIRS. 6. BEND STAPLES AT PEX POWDER ROOM 7. ADD FHA STRAPS AT 2 PLACES COMPRESSOR LINE 8. COMPLETE H20 B-VENT. 9. INSTALL STAB WIRE 10. FLEX IN ATTIC ACCESS. 11. EXTEND SECONDARY A/C DRAIN TO OUTSIDE. 12. CUT FELL FROM B-VENT 13. STRAP DRYER VENT 14. FHA STRAP 2ND FLOOR B-VENT |