Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM00790
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
01/30/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) GROUND AND NEUTRAL WIRES DAMAGED IN SERVICE PANEL BY OVER TORQUING-REPAIR ALL WIRES AND TORQUE PER PANEL SPECIFICATIONS. HAVE TORQUE DEVICE ON SITE FOR CITY INSPECTION 2) A/C CONDENSOR REQUIRES 30 AMP FUSE-50 AMP INSTALLED 3) A/C FLEX CONDUIT MUST BE SECURED WITHIN 12" OF DISCONNECT 4) SEAL HOLE IN GARAGE FIRE SEPERATION WALL WITH HARD SETTING FIRE RATED PLASTER-DO NOT USE SOFT SETTING DRYWALL MUD 5) STOPPED INSPECTION-TOO MANY ITEMS |