01/31/2007 BUILDING - FINAL Approved IVRS - Inspection :*
01/30/2007 BUILDING - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) GROUND AND NEUTRAL WIRES DAMAGED IN SERVICE PANEL BY OVER TORQUING-REPAIR ALL WIRES AND TORQUE PER PANEL SPECIFICATIONS. HAVE TORQUE DEVICE ON SITE FOR CITY INSPECTION
2) A/C CONDENSOR REQUIRES 30 AMP FUSE-50 AMP INSTALLED
3) A/C FLEX CONDUIT MUST BE SECURED WITHIN 12" OF DISCONNECT
4) SEAL HOLE IN GARAGE FIRE SEPERATION WALL WITH HARD SETTING FIRE RATED PLASTER-DO NOT USE SOFT SETTING DRYWALL MUD
5) STOPPED INSPECTION-TOO MANY ITEMS