Permit: T06CM00788

Parcel: 141095350

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
01/31/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
10/18/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) HOLDOWN EAST SIDE OF PATIO DOOR NOT ON SHEARWALL. 2) PROVIDE RETROFIT HOLDOWN
3) OK TO DRY IN
10/16/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING CLIPS ON EXTERIOR WALLS-CARPENTER SUPER MARKED AREAS AS JOB WAS WALKED
2) MISSING DIAGONAL BRACE, BACK WALL
3) NEED DBL 2 X AT ALL SHEAR WALL CORNERS
4) MISSING STRAPS GLU LAM STAIR WAY
5) SHEARWALL STAIR WAY NEEDS LONGER STRAPS
6) GABLE PER 2/D2
10/12/2006 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER SUPER