Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06CM00768

Parcel: 120080960


Addresses:

4535 S 12TH AV #101

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/09/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
03/08/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
BACKFLOW TEST AND PERMIT OK
T&P DRAIN MUST GRAVITY DRAIN WITHOUT TRAP
SUPPORT EXPANSION TANK
PROVIDE PROPER CLEAN OUT PLUGS TO RECEIVE SCREW