Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 02/10/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 03050 - 15 PSI TEST NOW PIPING FROM EXISTING PIPING ON ROOF TO WATER HEATER ONLY (OK) -- GAS IS ON CONTRACTOR TO VERIFY NO LEAKAGE OF GAS AT FINAL CONNECTION TO WATER HEATER OK TO CONNECT - APPROVED 03090 - 1. PROVIDE CORRECT SUPPORTS & SECURE PIPING ON ROOF 2. SECURE GAS PIPING IN WATER HEATER CLOSET 3. PROVIDE 3-GALV SCREWS AT EACH JOINT OF FLUE VENT PIPING. 4. PROVIDE ROCK FILLED DRY WORK AT T&P 90 DEG. TERMINATION |