Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/TEST
Permit Number - T06CM00757
Inspection Description - PLUMBING - MEDICAL GAS/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2006 | PLUMBING - MEDICAL GAS/TEST | Approved | IVRS - Inspection :* | |
08/17/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* NITROUS AND O(2) W/150 PSI TEST, LABELING COMPLETE MV W/130 PSI TEST, LABELING OK SECURE MV SUPPLY STUBOUT REPAIR HW INSULATION WHERE MELTED AND SEAL JOINTS. |
|
08/15/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
08/02/2006 | PLUMBING - MEDICAL GAS/TEST | Not ready for Inspection | IVRS - Inspection :* PLUMBER WILL START PIPING LATER THIS WEEK CALL FOR INSPECTION DAILY ONCE WORK BEGINS |
|
06/21/2006 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1. INSTALLER HAS STARTED DAILY LOG. 2. VACUUM PIPING U.G OK TO COVER 3. REDLINES TO ALLOW C.A PIPING TO BE LOOPED FROM ADJACENT PARTITION -- OK TO COVER SUBJECT TO APPROVED PLAN. |