Permit: T06CM00754

Parcel: 141095210

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T06CM00754

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2007 BUILDING - FINAL Approved IVRS - Inspection :*
01/31/2007 BUILDING - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Property line sewer missing proper cleanout-4" does not fit 3" line
Refee
01/29/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PROPERTY LINE SEWER CLEANOUT
2) PROVIDE 2" CLEARANCE BETWEEN WEEP SCREED AND CONCRETE, WEEP SCREED COVERED WITH CONCRETE
3) WIRES DAMAGED BY OVER TORQUE-REPAIR ALL WIRES AND TORQUE PER SPECS
4) NO GAS BOND ? MISSING EXPOSED CLAMP
5) PROVIDE 4" CLEARANCE BETWEEN WEEP SCREED AND SOIL
6) A/C CONDENSOR PAD MUST BE 3" ABOVE SOIL
7) SEAL WALL HOLE BY W/H S.O.V.
8) PROVIDE 30" VERTICAL ACCESS TO FURNACE AND SECURE GAS LINE SUPPORT