Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM00754
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
06/23/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THIS HOUSE AND PER FRAMER ALL HOUSES IN THIS DEVELOPMENT HAS USED UNDERSIZED FRAMING NAILS. PLAN CALLS FOR 16D NAILS BUT 3" X .131 10D NAILS HABE BEEN USED THROUGHOUT. YOU MUST HAVE ENGINEER OF RECORD EVALUATE FRAMING HARDWARE USED ON THIS SITE AND PROVIDE REPORT TO CITY OF TUCSON WITH APPROPRIATE REPAIR 2) TECO NAILS CANNOT BE USED THRU OSB MUST USE 8D COMMON SINKERS 3) CS STRAPS MUST BE ATTACHED TO STUDS THAT ARE CLIPPED TO PLATES 4) MISSING POSTS FOR GIRDER TRUSS 5) OSB CANNOT BE BETWEEN PORCH LEDGER AND STUDS 15/D7 6) LEDGER ON PORCH MISSING H2.5 CLIPS 15/D7 7) SAFETY BRACES MUST BE INSTALLED WITH 16D NAILS-10D USED 8) NO LADDER TO ROOF |