Permit: T06CM00746

Parcel: 141095070

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
06/22/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/08/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DIAGONAL BRACES REQUIRE 2-16D NAILS ON END
2) EAST WALL SOUTH END MISSING DIAGONAL BRACES
3) WEST T-10 TRUSS INSTALLED BACKWARD. PROVIDE CITY APPROVED ENGINEERING REPAIR
4) CLIP 3 PT BEARING TRUSSES PER 3/D2
5) MANY ROOF PANELS NOT NAILED