Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2006 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 03/09/2006 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) YOU ARE IN VIOLATION OF IBC SECTION 1907.7.1; YOUR BURSTING STEEL DOES NOT HAVE SUFFICIENT CONCRETE COVER YOU ARE REQUIRED TO HAVE 1 1/2". NIPPLES COVERED WITH PLASTIC ON TENDONS ARE TO BE 3/4" COVERED ANCHORS MAY NOT BE TOUCHING FORMS |
|
| 03/07/2006 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* CANCELLED |