Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM00716
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2007 | FRAMING | Approved | IVRS - Inspection :* | |
02/06/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REPAIR FIRE STOP A/C CHASE MASTER TOILET 2) CHECK NAILING BOTTOM PLATES ALL 2ND FLOOR EXTERIOR WALLS 3) CAULK A/C WIRE 4) REPAIR HOLE FRONT DOOR 5) PROVIDE MORE CLEARANCE AT WEEP SCREED FRONT PORCH 6) WIRE FOR PENINSULA CUT 7) NO DWV TEST 8) SUPPORT ABS EVERY 4' 9) NAIL OFF FHA STRAP AT MAIN ENTRANCE SERVICE 10) NEED FHA STRAPS 1 1/2 ABS MASTER CLOSET 11) NAIL OFF ALL HOLES FHA STRAPS AT GAS PIPE 12) PRESSURE TEST OK 13) WATER HEATER B-VENT MUST HAVE MINIMUM PITCH OF 30 DEGREE 14) SUPPLY AIR DUCT BEDROOM 3 SEVERLY RESTRICTED |
|
01/31/2007 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) PROVIDE 2" CLEARANCE FOR STUCCO WEEP SCREED AT ENTRY 2) NO GAS TEST 3) NO DWV TEST 4) STOPPED INSPECTION |