Permit: T06CM00703

Parcel: 12702278B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/24/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/23/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WATER TEST ON DWV OK
REMOVE CONCEALED TIP AT GREASE TRAP
INSTALL SWEEPS ON HORIZONTAL TRAP ARMS AT LAV AND HAND SINK.
PROVIDE VENT FOR FLOW CONTROL.
SUPPORT HORIZONTAL ABS AT BRANCH CONNECTION AND AT 4' USE APPROVED PIPE SUPPORTS.
PROVIDE PERM CAPS FOR DEMO FIXTURES.
CLEAN OUT EXTENSIONS REQUIRE WYE BRANCH FITTINGS.