Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM00680
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
11/09/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* EACH CARBONATOR REQUIRES SEPARATE BACKFLOW PROTECTION WITH CERTIFICATION. WASH & RINSE TO BE SEPARATE FROM SANITIZE BOWLS OF 3-COMPARTMENT SINKS. PROVIDE DRAINAGE FITTINGS ON INDIRECT DRAINS WITH P-TRAPS ON INDIRECT DRAINS OVER 5' IN LENGTH. PROVIDE LONG RADIUS FITTING FOR AIR ADMITTANCE VALVE AT BAR HAND SINK. FINISH INSULATION IN WATER HEATER AREA NON-CARBONATED BEVERAGE DISPENSER REQUIRES DOUBLE CHECK TESTABLE BACKFLOW DEVICE. |