Permit: T06CM00680

Parcel: 14117007F


Addresses:

7585 S HOUGHTON RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM00680

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
11/09/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
EACH CARBONATOR REQUIRES SEPARATE BACKFLOW PROTECTION WITH CERTIFICATION. WASH & RINSE TO BE SEPARATE FROM SANITIZE BOWLS OF 3-COMPARTMENT SINKS.
PROVIDE DRAINAGE FITTINGS ON INDIRECT DRAINS WITH P-TRAPS ON INDIRECT DRAINS OVER 5' IN LENGTH.
PROVIDE LONG RADIUS FITTING FOR AIR ADMITTANCE VALVE AT BAR HAND SINK.
FINISH INSULATION IN WATER HEATER AREA
NON-CARBONATED BEVERAGE DISPENSER REQUIRES DOUBLE CHECK TESTABLE BACKFLOW DEVICE.