Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM00669
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 01/16/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SECURE PIPE STANDS 2. VENT 5 PSI TO REGULATORS, WEATHER & BUG PROOF VENT TERMINATIONS WITH LABELING TAGS. 3. VALVING TO BE CORRECT 4. 2ND STAGE CONTROL TO BE VENTED CORRECTLY 5. COMPLETE WATER TO COOLER SUPPLIES. |
|
| 11/29/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES FROM 11/28/06 INSPECTION & COMPLY HAVE A CONTACT PERSON ON SITE AT FUTURE INSPECTION FAILURE TO DO SO SHALL RESULT IN REFEE. |
|
| 11/28/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SHALL READ REGULATOR TAG AND INSTALL APPROVED MATERIAL FOR DIRECTION ON TAG MEETING 2003 UPC REQUIREMENTS FOR ALL REGULATOR VENTS. 2. SHALL PROVIDE A TEE FITTING FOR PRESSURE GAUGE UPSTREAM OF GAS INLET VALVE TO EAST UNIT. 3. HOSE BIB REQUIRES VACUUM BREAKER (IMMEDIATELY!) 4. PROVIDE ROOF ACCESS FOR WATER PIPING TERMINATION. 5. SHALL SEE INSTALL OF CORRECT REGULATOR AT METER AREA PER PLAN FOR FINAL. 6. GAS PIPING TO BE SUPPORTED AT PAINT BOOTHS AREA. 7. WATER PIPING SHALL NOT BE RAN OVER ELECTRICAL PANEL SPACE. |
|
| 11/16/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |