Permit: T06CM00669

Parcel: 13502007C


Addresses:

1441 S WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM00669

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
01/16/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SECURE PIPE STANDS
2. VENT 5 PSI TO REGULATORS, WEATHER & BUG PROOF VENT TERMINATIONS WITH LABELING TAGS.
3. VALVING TO BE CORRECT
4. 2ND STAGE CONTROL TO BE VENTED CORRECTLY
5. COMPLETE WATER TO COOLER SUPPLIES.
11/29/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES FROM 11/28/06 INSPECTION & COMPLY
HAVE A CONTACT PERSON ON SITE AT FUTURE INSPECTION
FAILURE TO DO SO SHALL RESULT IN REFEE.
11/28/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL READ REGULATOR TAG AND INSTALL APPROVED MATERIAL FOR DIRECTION ON TAG MEETING 2003 UPC REQUIREMENTS FOR ALL REGULATOR VENTS.
2. SHALL PROVIDE A TEE FITTING FOR PRESSURE GAUGE UPSTREAM OF GAS INLET VALVE TO EAST UNIT.
3. HOSE BIB REQUIRES VACUUM BREAKER (IMMEDIATELY!)
4. PROVIDE ROOF ACCESS FOR WATER PIPING TERMINATION.
5. SHALL SEE INSTALL OF CORRECT REGULATOR AT METER AREA PER PLAN FOR FINAL.
6. GAS PIPING TO BE SUPPORTED AT PAINT BOOTHS AREA.
7. WATER PIPING SHALL NOT BE RAN OVER ELECTRICAL PANEL SPACE.
11/16/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*