Permit: T06CM00669

Parcel: 13502007C


Addresses:

1441 S WILMOT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/16/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CLEAN EXCESS PAINT FROM DEVICES 110.12
2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
3) SUPPORT JUNTION BOX AND REPLACE MISSING COVER BOTH #2
4) TIGHTEN LOOSE FITTING-FIRE ALARM CARFLEX
5) FIXTURES NOT PER PLANS
6) M/C CABLE TO TERMINATE TO BELL
7) PLEASE HAVE ELECTRICIAN PRESENT TO OPEN EQUIPMENT
8) BEAM CLAMP NOT LISTED FOR GROUNDING