Permit: T06CM00665

Parcel: 140294790


Addresses:

3873 E SUN VIEW CT


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM00665

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2006 FRAMING Approved
09/07/2006 FRAMING Partial Approval IVRS - Inspection :*
PENDING ON OTHER TRADES
09/01/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
NOT READY PER SUPER
08/29/2006 FRAMING Partial Approval IVRS - Inspection :*
1) SEAL LATHE AROUND EXHAUST VENTS
2) 1" CLEARANCE TO WATE HTR B-VENT
3) ATTIC ACCESS IN GARAGE
4) FILL DWV
5) RPS STRAPS REQUIRED AT OVER BORED PLATES IN KITCHEN
6) INSUFFICIENT NAILING IN STRAPS AT A/C COPPER
7) SECURE RECEPTACLE BOX BY WINDOW IN BED #2
8) NO WIRE IN RECEPTACLE BOX SOUTH M. BED WALL
9) INSULATION DAMAGED AT A/C COPPER 2ND FLOOR
10) INSULATION SHIELD REQUIRED IN ATTIC AT B-VENT PER 80-AD4
11) PLAN CALLS FOR 2" CLEANOUT IN BOTH 2ND FLOOR BATHROOMS