Permit: T06CM00663

Parcel: 140295840

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM00663

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/25/2006 FRAMING Approved IVRS - Inspection :*
10/23/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY DENNIS
10/19/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPAIR CONCRETE S.W. PORCH POST
2) 2ND 2 X 6 NORTH OF SGD EXTREMELY WARPED
3) NAIL OFF LANDING LEDGERS
4) CLEAR WIRE FROM GARAGE LIGHT; CAULK LIGHT AND A/C WIRES
5) REPAIR WIRE AT FRONT DOOR
6) ADD RECEPTACLE TO RIGHT OF HALL BATH LAVS AND ADDITIONAL LIGHT
7) DWV TEST OK
8) SUPPLY TEST NOT DONE
9) NAIL OFF FHA STRAPS AT LINE SETS
10) NAIL OFF FHA STRAPS AT TOP PLATES 8 NAILS EACH SIDE
11) CONNECT FURNACE B-VENT
12) CLARIFY 4-2 X 4'S AND 3-2 X 4'S AT GLU LAM AND BUILT UP BEAM PAGE S2 ELEVATION A + B
10/12/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 01025 INSPECTION NEVER APPROVED
2. SEVERAL WIRES CUT @ HOME RUN
3. NO GAS PRESSURE TEST
4. STUCCO MESH NOT READY
5. INSPECTION STOPPED!

THIS IS NOT A COMPLETE LIST.