Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM00657
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2006 | FRAMING | Approved | IVRS - Inspection :* | |
10/23/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY DENNIS |
|
10/19/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN RED HEADS 2) SOME FIRE BLOCKING MISSING AT STAIR LAUNDRY 3) INSULATE BEHIND MASTER TUB 4) COMPLETE REPAIRS AND CAULKING AT A/C LINE SETS AND WIRES 5) SEAL STAPLES KITCHEN BELOW VENT DUCT 6) RESTAPLE WIRES IN KITCHEN 7) REMOVE RECPETACLE BELOW BAR TOP KITCHEN 8) NO DWV TEST 9) SUPPLY OK 10) GAS PIPE AND WIRE BLOCKING ATTIC ACCESS 11) NAIL OF FHA STRAPS AT LINE SETS |
|
09/14/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE 1" CLEARANCE TO B-VENT AT WATER HTR 2) FILL DWV 3) TIGHTEN RED HEADS 4) 2 X 6 EXTERIOR SHEARWALL STUD OVER BORED IN KITCHEN 5) RPS RE-INFORCING STRAP REQUIRED AT OVER BORED TOP PLATE IN KITCHEN 6) SEAL VAPOR BARRRIER 7) FIRE STOP ALL 2ND FLOOR PENETRATIONS 8) FIRE BLOCK STAIR LANDING 9) WIRE EXHAUST FAN IN 1ST FLOOR BATH 10) STOPPED INSPECTION |