Permit: T06CM00584

Parcel: 116275150

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM00584

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/15/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
06/14/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. DUTCHMEN INSTALLED TO REPAIR WCF OK
2. TUB OK
06/08/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CALL FOR AND HAVE APPROVED ALL INSPECTIONS NOT YET APPROVED.
REMOVE WCS FOR CLOSET FLANGE INSPECTION - SECURE TO FLOOR ADD DUTCHMENT GARDEN TUB DRAIN.
FILL TUB TO OVERFLOOR LEVEL.
CLEAN OUTS IN CONCRETE WALKWAY SHALL BE BRASS BODY.
CLEAN OUT PLUGS USED TO SECURE COVERS SHALL BE DESIGNED FOR SUCH USE, PROVIDE FIANL GAS PRESSURE TEST ON SYSTEM.
GAS APPLIANCES INSTALLED IN A GARAGE ARE REQUIRED TO BE PROTECTED FROM VEHICULAR DAMAGE. DRYER SHALL BE 18" ABOVE FLOOR OR PROVIDE LISTING ALLOWING OTHER INSTALLATION. GAS DRYER IS ON SITE. WATER HEATER INSTALLED ON A PLATFORM MADE OF MATERIALS THAT COULD BE DAMAGED IF A LEAK WERE TO OCCUR SHALL HAVE A DRAIN PAN INSTALLED WITH A DRAIN. CORRECT SLOPE ON KIT. SINK TRAP ARM. ALSO TRAP ARM CHANGES OF DIRECTION OVER 90 DEGREES REQUIRE A CLEAN OUT. SECURE DW