Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM00584
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2006 | PLUMBING - INTERMEDIATE | Approved | YARD WATER REQUIRED TO HAVE CLEAN COMPACTABLE DIRT. ALL CLOTHES DRYERS ARE REQUIRED TO BE ELEVATED 18" ABOVE THE FLOOR IN A GARAGE. I RECOMMEND THAT YOU RAISE YOUR GAS VALVE AND DRYER VENT BOX TO AVOID PROBLEMS INSTALLING DRYER. DRYERS NOT ELEVATED IN A GARAGE MAY RESULT IN DEATH, EXPLOSION OR FIRE. |
|
04/18/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER LINE IN COLUMN OK YARDWATER LINE WILL NEED TO BE UNCOVERED FOR INSPECTION. VACUUM BREAKER REQUIRED. LAVATORY TRAP ARM SHALL BE 1 1/2" FROM POINT OF VENT. OK TO COVER WALL EXCEPT FOR CORRECTION AT LAVATORY. CONTRACTOR NEEDS TO BE AWARE OF SECS. 305.3 AND 305.5 OF THE INTERNATIONAL FUEL GAS CODE. |
|
04/14/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/11/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* GAS PIPING PRESSURE TEST OK REDLINE PLAN FOR CHANGE OF WATER SERVICE LOCATION. UNCOVER WATER PIPING AT SERVICE. PROVIDE PRESSURE TEST ON WATER PIPING. TEST ICE MAKER LOOP ALSO, SECURE L. BOX. SECURE ICE MAKER BOC. REX TUBING MUST BE SECURED TO STAY 12" AWAY FROM RECESSED LIGHT CAN. OK TO INSULATE HOT. PROVIDE A WATER OR AIR TEST ON DWV PIPING. PROVIDE A WATER TEST ON TUB CONNECTIONS. PROVIDE A FHA DRAIN FOR SHOWER, PROVIDE CLOSET FLANGES. (CLOSET FLANGES, FHA DRAIN AND GARDEN TUB DRAIN CAN BE INSPECTED LATER) PROVIDE PROPER DRAINAGE FITTINGS AND SIZE FOR TRAP ARMS. PROVIDE STANDARD P TRAP AT LAUNDRY. REDLINE CHANGE OF GAS PIPING. WATER HEATERS INSTALLED ON A SUB-FLOOR REQUIRE A DRAIN PAN W/ A DRAIN. |