Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM00580
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/26/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/22/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* DOOR IS LOCKED |
|
02/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLEXIABLE CORD FOR DRIVE UP WINDOW NOT TO PASS THROUGH WALL-NEC 400.8 2) RUN DATA CORD TO SAFE IN A NEAT AND WORKMAN LIKE MANNER-NEC 800.6 3) EXTERIOR EMERGENCY EGRESS LIGHTS NOT IN 4) PELCO MASTER POWER SUPPLY PANEL DOES NOT HAVE PROPER FRONT WORKING CLEARANCE-NEC 110.26 5) ALARM PANEL HAS NO EARTH GROUND TO IT ? NEC 110.3 B 6) MAKE SURE SERVICE DISCONNECTS/PANELS PROPERLY IDENTIFIED FOR NEW SPACE, AND PROPERLY FUSED 7) PROVIDE LADDER FOR ROOF INSPECTION |