Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM00580
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/20/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/15/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS AND BATHROOM LIDS |
|
11/13/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. REMOVE ALL UNUSED/ABANDONED WIRING FROM WALLS, CEILINGS. 2. SECURE ALL MC WITHIN 12" OF TERMINATIONS. 3. TIGHTEN ALL GROUND SCREWS AND DON'T OVERLAP CONDUCTOR ON SCREW. 4. REMOVE DOUBLE BARREL MC CONNECTOR IF NOT USED AND SEAL ALL UNUSED OPENINGS. 5. PROVIDE BACK SUPPORT FOR ALL BOXES (SWITCH/RECEPTACLE) 6. USE NAIL PLATES NOT 4 SQUARE COVERS - ANYWHERE 1 1/4 OR LESS TO STUD FACE. 7. IDENTIFY WHITE USED AS HOT 8. BATH LIGHTS MISSING AND COMPLETE RACEWAYS ABOVE HARD LIDS. |