Permit: T06CM00577

Parcel: 14117005C


Addresses:

7385 S HOUGHTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T06CM00577

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2008 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
03/12/2008 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) HAD FIELD EVALUATION DONE FOR BRACING OF GEAR PASED. WAITING FOR COPY OF REPORT
2) OK LIGHTS IN OUTDOOR SOFFITS
3) RECEIVED LETTER OF TORQUE
03/11/2008 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
03/03/2008 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
1. LABELING CANNOT BE CHANGED IN FIELD WITHOUT THIRD PARTY EVALUATION
2. PLEASE HAVE GEAR OPENED
02/11/2008 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
1. POST BOND FOR TEMP POWER FOR TEST
2. PROVIDE LETTER OF TORQUE
3. PLAN CALLS FOR SERVICE TO BE RATED 100KAIC
4. SWITCHGEAR TO BE BOLTED DOWN TO CONCRETE
5. INSTALL BELL ENDS ON PVC ENTERING SWITCHGEAR
6. BOND WATER AND GAS WHEN INSTALLED