Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T06CM00577
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2008 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
03/12/2008 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1) HAD FIELD EVALUATION DONE FOR BRACING OF GEAR PASED. WAITING FOR COPY OF REPORT 2) OK LIGHTS IN OUTDOOR SOFFITS 3) RECEIVED LETTER OF TORQUE |
|
03/11/2008 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* | |
03/03/2008 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* 1. LABELING CANNOT BE CHANGED IN FIELD WITHOUT THIRD PARTY EVALUATION 2. PLEASE HAVE GEAR OPENED |
|
02/11/2008 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* 1. POST BOND FOR TEMP POWER FOR TEST 2. PROVIDE LETTER OF TORQUE 3. PLAN CALLS FOR SERVICE TO BE RATED 100KAIC 4. SWITCHGEAR TO BE BOLTED DOWN TO CONCRETE 5. INSTALL BELL ENDS ON PVC ENTERING SWITCHGEAR 6. BOND WATER AND GAS WHEN INSTALLED |