Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2007 | BUILDING - FINAL | Approved | ||
| 06/04/2007 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) BLDG FINAL IS PARTIALLED UNTIL ROOF STAIRS COMPLETE 2) ALL ELSE OK |
|
| 06/01/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL GROUND BAR ONTO PANEL JACKET IN GARAGAE 2) COLOR ALL HOT WHITES BLACK IN BOTH PANELS 3) SEPERATE DIFFERENT SIZE WIRES THAT ARE DBL OR TRIPPLE TAPED IN MAIN PANEL 4) CAP EXTERIOR FIREPLACE GAS LINE 5) ALL EXTERIOR LIGHTS THAT ARE NOT UNDER ROOF MUST HAVE BULBS SHADED 6) DIAGRAM EXTERIOR GFI COVERAGE 7) OUTLETS ON NORTH COUNTER MUST BE GFI 8) NOTE: NEED ROOF STAIRS BEFORE FINAL APPROVAL |