Inspection History Details
Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
Permit Number - T06CM00544
Inspection Description - SHEET ROCK NAILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2006 | SHEET ROCK NAILING | Approved | IVRS - Inspection :* | |
05/04/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* OK TO TAPE WALLS & CEILINGS THAT ARE "NOT" FIRE BARRIERS, FIRE BARRIERS MUST BE CAULKED IN ACCORDANCE WITH ** SEE NOTES BELOW #'S 104, 203, 204 |
|
05/02/2006 | SHEET ROCK NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LISTED FIRESTOP SYSTEM FOR AREA SEPARATION WALLS AND INSTALL SYSTEM. 2. 2 LAYERS 5/8 TYPE X REQUIRED ON CEILING OF #104 |
|
05/01/2006 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection :* EXCLUDING NORTH PARTY WALL (NEEDS TO BE 5/8" THICK) 1. PLEASE CAULK ANY JOINTS LARGER THAN 1/16" & ANY PENETRATIONS WITH A U.L LISTED, INTUMESCENT FIRE CAULK. |