Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM00532
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/28/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* AIR TEST WASTE & VENT OK WATER PIPING OK |
|
07/06/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES DATED 5/12/06 |
|
07/03/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE ACCESS NO ACCESS 9:10 AM |
|
06/30/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/12/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE CORRECT DRAINAGE FITTING FOR LAVS DBL SANTEE IS NOT CORRECT. 1/4 BONDS ARE NOT. 1 1/2 DRAIN ARM MAXIMUM OF 42". 2. PROVIDE TEST ON WASTE & VENT AND WATER PIPING. 3. WHAT IS 3/4" STUBS TO EAST OF RESTROOM FOR? PROVIDE REVISED PLAN OR REMOVE THIS WATER PIPING. |