Inspection History Details
Inspection Status: Approved
Inspection History: ROOF NAILING
Permit Number - T06CM00531
Inspection Description - ROOF NAILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2006 | ROOF NAILING | Approved | IVRS - Inspection :* | |
05/25/2006 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REPLACE EXCESSIVELY SPAULED HOLDOWNS WITH APPROVED RETRO FITS 2) RE-NAIL ALL SHEATHING-NAIL HEADS SET TO DEEP AND OR NOT DEEP ENOUGH 3) HOLDOWNS MISSING REAR-NEED ENGINEER APPROVAL RETRO FIT HOLDOWNS AND SPECIAL INSPECTION ON SAME 4) GARAGE BEAM SCARF CUT NOT TO DETAIL 1/6 EXCESSIVELY CUT 5) CS 16 STRAPS MISSING 2ND FLOOR FRONT WINDOW BOTH SIDES 6) SHEARWALL TRANSFER INCOMPLETE 7) SHEARWALLS REQUIRE DBL STUDS EACH END OF PANEL 8) CS20 STRAPS TO BE INSTALLED ON ENDS OF S.W. PANELS ACCROSS 1ST/2ND FLOOR SPLIT 9) ALSO NEED LADDER 10) STOPPED INSPECTION INCOMPLETE 11) RECALL WHEN READY |