Permit: T06CM00528

Parcel: 141094890

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM00528

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/25/2006 FRAMING Approved IVRS - Inspection :*
07/21/2006 FRAMING Partial Approval IVRS - Inspection :*
1) LEAK ON 3" COTTAGE T STACK IN GARAGE
07/18/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DWV LEAK 3" STACK
2) REVERSE PITCH AT CONDENSATE
07/11/2006 FRAMING Cancelled IVRS - RI canceled
07/11/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE 1" TO COMBUSTIBLE MATERIAL AT WATER HEATER VENT
2) WATER HEATER B-VENT MUST HAVE 30 DEGREE RISE
3) NO GAS PRESSURE TEST
4) 12/D6 NOT COMPLIED WITH AT GARAGE
5) NO DWV WATER TEST
6) SHEARWALL 4 REQUIRES ENDS AND EDGGES AT 4" ON CENTER
7) REVERSE PITCH ON CONDENSATE
8) SHEARWALL ANCHOR BOLTS MISSING
9) SECOND FLOOR STRAPS MISSING
10) NAIL PROTECT ELECTRIC