Permit: T06CM00527

Parcel: 111083580

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM00527

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/30/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL
03/07/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUND ALL METAL BOXES NEC 250.4 (2)
2. INSTALL NAIL PLATES AS NEEDED NEC 300.4 (D)
3. USE PROPER CONNECTOR WHERE ROMEX ENTERS ENCLOSURES NEC 110.3 (B)
4. INSTALL KO BLANKS AS NEEDED NEC 110.12 (A)
5. USE WIRE NUTS ONLY FOR CONDUCTORS LISTED FOR USE (AMOUNT AND SIZE) NEC 110.3 (B), NEC 110.14
6. PROVIDE AN EQUIPMENT GROUND FOR SUB-PANELS
NEC 408.20, NEC 250.110
7. FINISH MAKE UP
8. REMOVE DISCARDED WIRING
9. IDENTIFY NEUTRAL (WHITE) USED AS HOT
10. FRAME IN OPENINGS FOR J-BOXES