Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM00527
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL |
|
| 03/07/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUND ALL METAL BOXES NEC 250.4 (2) 2. INSTALL NAIL PLATES AS NEEDED NEC 300.4 (D) 3. USE PROPER CONNECTOR WHERE ROMEX ENTERS ENCLOSURES NEC 110.3 (B) 4. INSTALL KO BLANKS AS NEEDED NEC 110.12 (A) 5. USE WIRE NUTS ONLY FOR CONDUCTORS LISTED FOR USE (AMOUNT AND SIZE) NEC 110.3 (B), NEC 110.14 6. PROVIDE AN EQUIPMENT GROUND FOR SUB-PANELS NEC 408.20, NEC 250.110 7. FINISH MAKE UP 8. REMOVE DISCARDED WIRING 9. IDENTIFY NEUTRAL (WHITE) USED AS HOT 10. FRAME IN OPENINGS FOR J-BOXES |