Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 01/25/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE FEED IS TO SMALL FOR THE LOAD 2) CMT BRANCH CIRCUIT STILL CONNECTED TO BREAKERS 3) UNGROUNDED SERVICE, DISCONNECT FACING FENCE NEEDS 3' CLEARANCE IN FRONT OF IT 4) PROVIDE INSPECTION CERTIFICATE OF APPROVAL FOR MH FROM STATE OF AZ 5) OBTAIN A LICENSED CONTRACTOR TO MAKE ELECTRICAL CORRECTIONS |