Permit: T06CM00512

Parcel: 115221130

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/28/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK TO CLEAR POWER ON #1 ECO
WILL NOTIFY TEP
09/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE NEUTRAL TO GROUND BAR IN PANEL
2. INSTALL PNL SCHEDULES & COVERS
3. MISSING FIXTURE AT END OF HALL IN #2
4. GFI COVER IN BATH #2 MISSING
5. OUTSIDE RECEPTACLES REQUIRE BUBBLE COVERS ON RECEPTACLES EVEN THOUGH NOT IN USE.
6. AC DISCONNECTS TAPE WHITE.