Permit: T06CM00494

Parcel: 141094910

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/21/2006 FRAMING Approved IVRS - Inspection :*
07/18/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GAS LINE MUST TERMINATE WITHIN 36" OF FURNACE CONNECTION
2) HALL BATH DIRTY ARM CANNOT EXCEED 42" IN LENGTH AND 1 1/2" IN DIAMETER UPC 1002, TABLE 10-1 AND TABLE 7-3
07/10/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LATHE NOT COMPLETE
2) SHEARWALLS MISSING ANCHOR BOLTS
3) MAX ALLOWED LAV DIRTY ARM 1 1/2" X 42" LONG
4) REPLACE HALL BATH ARM
6) SECURITY WIRES CANNOT BE IN ATTIC ACCESS
7) FURNACE GAS LINE MUST TERMINATE WITHIN 36" OF FURNACE CONNECTION
8) 1" CLEARANCE TO B-VENT