Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM00490
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* NEED PLAN REVISION FOR CHANGES TO WATER SERVICE. RED LINE APPROVED PLAN FOR INSPECTION BEFORE COVERING. |
|
02/14/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. TOILETS STILL NOT REMOVED. 2. NOTE: EXTERIOR HOSE BIB TO BE FLUSH MOUNTED SILCOCK |
|
02/01/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) MAKE ALL INSPECTION AREAS ACCESSIBLE 2) REMOVE WATER CLOSETS FOR CLOSET RING INSPECTION-SEE NOTE #4 FROM 06/23/06 |
|
06/23/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. GAS PRESSURE TEST OK 2. ABS DWV THRU ROOF OK WATER TEST OK 3. OK TO INSULATE HOT 4. NEED TO SEE CLOSET FLANGES 5. STRAP AND BRACE AS REQ'D |
|
06/22/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* ADDRESS NOT POSTED ROUGH PLUMBING NOT YET APPROVED 16 PSI ON 30 PSI GAUGE SECURE WATER STUB OUTS FHA STRAPS NEEDED |