Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM00490
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE HAVE ELECTRICAL CONTR. ON SITE NEXT INSPECTION WILL NEED TO VERIFY NOTES CORRECTED LAST INSP. 5/16/07 |
|
05/21/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED TO COMPLETE ALL CORRECTIONS FROM PREVIOUS INSPECTION BEFORE YOU CALL FOR FINAL. ALSO, POOL AREA TO BE CALLED IN FOR FINAL INSPECTION AS A CONDITION FOR FINAL FOR CLUBHOUSE. |
|
05/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEUTRAL #6 & SMALLER TO BE WHITE ENTIRE LENGTH - NEC 200.6 2. GROUND #6 & SMALLER TO BE GREEN OR BARE ENTIRE LENGTH - NEC 250.119 3. PROPERLY IDENTIFY PANEL DIRECTORY- NEC 408.4 4. WATER HEATER NOT WIRED, LIGHT BURIED 5. EMERGENCY LIGHTING TO BE FED BY LIGHTING CKT FOR THAT AREA - NEC 700.12 6. HAVE PLANS READY 7. PROVIDE GFI FOR ROOFTOP RECEPTACLE, FIX CONNETOR INTO DISCONNECT, IDENTIFY DISCONNECTS. 8. EXTERIOR LIGHTING NOT WORKING |