Permit: T06CM00490

Parcel: 10825002G

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/30/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE HAVE ELECTRICAL CONTR. ON SITE NEXT INSPECTION
WILL NEED TO VERIFY NOTES CORRECTED LAST INSP. 5/16/07
05/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NEED TO COMPLETE ALL CORRECTIONS FROM PREVIOUS INSPECTION BEFORE YOU CALL FOR FINAL.
ALSO, POOL AREA TO BE CALLED IN FOR FINAL INSPECTION AS A CONDITION FOR FINAL FOR CLUBHOUSE.
05/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEUTRAL #6 & SMALLER TO BE WHITE ENTIRE LENGTH -
NEC 200.6
2. GROUND #6 & SMALLER TO BE GREEN OR BARE ENTIRE LENGTH - NEC 250.119
3. PROPERLY IDENTIFY PANEL DIRECTORY- NEC 408.4
4. WATER HEATER NOT WIRED, LIGHT BURIED
5. EMERGENCY LIGHTING TO BE FED BY LIGHTING CKT FOR THAT AREA - NEC 700.12
6. HAVE PLANS READY
7. PROVIDE GFI FOR ROOFTOP RECEPTACLE, FIX CONNETOR INTO DISCONNECT, IDENTIFY DISCONNECTS.
8. EXTERIOR LIGHTING NOT WORKING