Permit: T06CM00490

Parcel: 10825002G

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM00490

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/20/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CALL FOR FINAL WHEN POWER IS ON
SERVICE HAS ALREADY BEEN CLEARED TO TEP
02/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INSTALL ADDRESS ON SERVICE, BOND WATER PIPE TO SERVICE AND INSTALL SERVICE RISER
2) OK CEILING COVER
02/02/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSPECTION FOR ABOVE CEILING ABOVE SUSPENDED CEILING ON INTERIOR
2) PROPERLY SUPPORT ALL LOW VOLTAGE WIRING, USE HANGERS ETC... WIRING NOT TO LAY ON EQUIPMENT OR GRID
3) MC TO BE SECURED WITHIN 12" OF TERMINATIONS NEC 330.30 C
4) GRID WIRE NOT TO BE USED TO SUPPORT MC-NEC 300.11 A
5) SUPPORT MC OFF GRID-NEC 300.11 A, 330.30, INSTALL SUPPORT WIRES FOR ALL FIXTURES
6) AT SERVICE: BOND WATER TO SERVICE-NEC 250.104, INSTALL SERVICE RISER AND INSTALL ADDRESS ON SERVICE
02/01/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) WIRING IN CEILING NOT COMPLETE-DO NOT CALL BEFORE READY OR A REINSPECTION FEE WILL BE CHARGED
2) PROVIDE LADDER FOR CEILING INSPECTION
06/26/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER ELECTRICAL IN WALLS AND HARD LIDS