Permit: T06CM00480

Parcel: 131010420


Addresses:

5002 E 22ND ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/31/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03/15/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE CORRECT SECURING OF PIPING TO BUILDING
2. INSTALL GAS PIPING AND APPROVED PLAN
3. PROVIDE WEATHER FLASHING FOR PIPE PENETRATION THRU ROOF.
4. PROVIDE TEST GAUGE IN 1/10 POUND INCREMENTS
5. SUPPORT PIPING WITH APPROVED DEVICES & SECURE PROPERLY ON HORIZONTAL TO BUILDING.
03/14/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/07/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
- GAS PIPE MUST BE STRAIGHT & ON A FIRM BED
- PROVIDE MIN. 10 LB. PRESSURE TEST
- PROVIDE APPROVED GAS SHUT OFF VALVES
- PROVIDE SUPPORT UNDER EXPOSED GAS PIPE
- PROVIDE APPROVED PLANS
03/03/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 8:37 AM-NO ACCESS
2) HAVE AN ADULT PRESENT 7:00 AM-3:30 PM TO PROVIDE ACCESS