Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* PLUMBING FINAL OK |
|
| 10/30/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CORRECT BACK PITCH ON CONTINUOUS WASTE |
|
| 10/26/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE SEDIMENT TRAP AT WATER HEATER GAS INLET 2. SECURE DISHWASHER DRAINAGE HOSE WITH HIGH LOOP CLAMP. 3. PROVIDE MINIMUM RISE FOR WATER HEATER VENT. 4. WEATHER SEAL ROOF TOP PIPE FLASHINGS. 5. SUPPORT GAS PIPING ON ROOF WITH SUPPORTS THAT MAKE CONTACT WITH ROOF SURFACE. |
|
| 10/25/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |