Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM00441
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SMOKE DETECTORS REQUIRE ARC FAULT PROTECTION AND PULL BATTERY TABS-NEC 210.12(B) 2) CORRECTLY IDENTIFY WASHER CKT IN PANEL-NOT LAUNDRY ROOM-NEC 408.4 3) PANEL DIRECTORY IS NOT LABELED CORRECTLY-NEC 408.4 4) DISHWASHER/DISPOSAL CKTS NEED TWO POLE BREAKER WHEN ON THE SAME YOKE-NEC 210.4(B) 5) PROVIDE ROOF ACCESS 6) GO THRU OTHER UNITS AND CHECK FOR THESE VIOLATIONS |
|
06/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |