Permit: T06CM00441

Parcel: 11615194B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SMOKE DETECTORS REQUIRE ARC FAULT PROTECTION AND PULL BATTERY TABS-NEC 210.12(B)
2) CORRECTLY IDENTIFY WASHER CKT IN PANEL-NOT LAUNDRY ROOM-NEC 408.4
3) PANEL DIRECTORY IS NOT LABELED CORRECTLY-NEC 408.4
4) DISHWASHER/DISPOSAL CKTS NEED TWO POLE BREAKER WHEN ON THE SAME YOKE-NEC 210.4(B)
5) PROVIDE ROOF ACCESS
6) GO THRU OTHER UNITS AND CHECK FOR THESE VIOLATIONS
06/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*