Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/13/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. LAUNDRY SWITCH BOX IS OVERFILLED. 2. NEED NAIL PLATES IN KITCHEN 3. SOME BOXES ARE NOT NAILED ON ALL THE WAY OR CROOKED. 4. HAVE CONDUCTORS COMPRESSED AGAINST GAS PIPE AT DISPOSAL. 5. CHECK THAT EQUIPMENT GROUND SCREWS ARE TIGHT IN METAL BOXES. 6. CABLES WITHIN 6' OF ATTIC ACCESS MUST BE PROTECTED. |