Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM00427
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/31/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. KITCHEN COUNTER OUTLETS NEED TO BE SERVED BY MINIMUM TWO 20 AMP CKT'S AND HAVE NO OTHER LOADS - NEC 210.52 (B) 2. PROTECT ROMEX AT ATTIC OPENING NEC 334.23 3. USE PROPER CRIMP TOOL FOR CRIMP SLEEVES NEC 110.3 (B) 4. OUTLETS REQUIRED 6' WITHIN BROKEN WALL LINE NEC 210.52 5. USE CONNECTOR FOR ROMEX ENTERING METAL BOX (OK TO COVER ELECTRICAL EXCEPT IN KITCHEN COUNTER AREA). |
|
03/29/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |