Permit: T06CM00427

Parcel: 11615194B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM00427

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/31/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. KITCHEN COUNTER OUTLETS NEED TO BE SERVED BY MINIMUM TWO 20 AMP CKT'S AND HAVE NO OTHER LOADS - NEC 210.52 (B)
2. PROTECT ROMEX AT ATTIC OPENING NEC 334.23
3. USE PROPER CRIMP TOOL FOR CRIMP SLEEVES NEC 110.3 (B)
4. OUTLETS REQUIRED 6' WITHIN BROKEN WALL LINE
NEC 210.52
5. USE CONNECTOR FOR ROMEX ENTERING METAL BOX
(OK TO COVER ELECTRICAL EXCEPT IN KITCHEN COUNTER AREA).
03/29/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*